ZJSHUYI Talk about three dual power supply configuration schemes. www.sh...

(1) If the two power sources are installed in the same place and share the same low-voltage power distribution cabinet, a four-pole switch shall be used for the incoming circuit or the switching circuit of the dual power sources. (2) The dual-circuit distribution transformers serve as backup power sources for each other, or the transformers and diesel generators serve as backup power sources for each other, and the neutral points of the transformers and generators are directly grounded nearby. If two sets of power supplies share a low-voltage power distribution cabinet, the incoming circuit should use a four-pole switch (3) If the two sets of power supplies are in the same room (common ground), but do not share low-voltage power distribution cabinets, the power transfer switch in the secondary power distribution equipment can be a three-pole switch Web: www.shuyitop.com; Tel/Fax: 0086-577-62840011 Wechat/WhatsApp: 008613355775769 #ZJSHUYI #Chinashuyi #shuyitop #swtiches #Dualpowertransferswitch #Dualpower