installation requirements 1. The installation and wiring of the soft starter should follow the corresponding installation standards and safety regulations. 2. It is strictly forbidden to wire the soft starter when it is powered on. 3. It is strictly forbidden to use a megohmmeter to measure the insulation resistance of the soft starter. 4. When the soft starter is working normally, it will automatically output bypass. 5. The soft starter must be connected to the load during debugging, which can be smaller than the actual load. 6. Active input is prohibited from the remote terminal of the soft starter. 7. When wiring the soft starter, the three-phase input power must be wired according to the specified phase sequence. 8. The number of soft starter starts is recommended not to exceed 20 times per hour. 9. The soft starter should be installed vertically, and should not be installed upside down, obliquely or horizontally, and the base of the installation should be firm and flat. www.shuyitop.com; Tel/Fax: 0086-577-62840011 WhatsApp: 008613355775769 #softstarter #motorsoftstar #softstarters #softstartechnology #softstartermarket #softstarterprice #ac powersoftstarterwithbuilt-inbypass #builtinbypasssoftstarter #singlephasemotorsoftstarter #ZJSHUYI #Chinashuyi